Installation Information for
150psi Rated Non-Retractable Injection Quills with Quick Release Coupler

Applies to BCK Series Injection Quills

 

PRECAUTIONS

Injection quills are designed to deliver a chemical solution feed to the interior of a pressurized water/process main. The following precautions should be taken to ensure proper and safe installation:

  • Become familiar with the components of the injector as listed below.
  • Verify that the injector being installed is compatible with the intended chemical feed.
  • Make sure to use the correct hex when using a wrench to install.
 

INSTALLATION INSTRUCTIONS  

CAUTION: Take care not to over tighten PVC housings. Damage caused by over tightening voids warranty.
  • Apply Teflon thread tape or suitable sealant to the Main Connection Thread of the injector.
  • Thread the quill into the main using the lower Installation Hex (See Component 7) into the service tap.
  • Connect chemical feed line to inlet thread located on the Female Half of the Quick Release Coupler.
 

DISCONNECTING THE QUICK RELEASE COUPLING

  • Pull back on the outer ring of the Female Half of the Quick Release Coupler.
  • While pulling back on the outer ring lift the Female Half up off the Male Half Nipple.
 

CONNECTING THE QUICK RELEASE COUPLING

  • Pull back on the outer ring of the Female Half of the Quick Release Coupler.
  • While pulling back on the outer ring push the Female Half down onto the Male Half Nipple. Once seated release the outer ring to lock the coupler into position.
 
Retractable Sampling Probe - 150psi

COMPONENTS

Female Half Quick Release Coupler

  1. Inlet Thread
  2. DO NOT use wrench on this hex
  3. Outer Ring

Male Half Quick Release Coupler

  1. Male Half Nipple
  2. DO NOT use wrench on this hex

Quill Housing

  1. Integrated Spring Loaded Ball Check Valve
  2. Installation Hex, use to tighten during install
  3. Main Connection Thread
  4. Solution Tube
 

For installation questions and assistance contact customer service at 1-800-957-2383

 