Installation Information for 250psi Rated Retractable Flanged Injection Quills

Applies to Series EB-180, EB-188, EB-182, EB-184, EB-185, and EB-186

 

PRECAUTIONS

Injection quills are designed to deliver a chemical solution feed to the interior of a pressurized water/process main. The following precautions should be taken to ensure proper and safe installation:

  • Become familiar with the components of the injector as listed below.
  • Minimize system pressures when retracting or inserting the Solution Tube.
  • Verify that the injector being installed is compatible with the intended chemical feed.
  • Ensure that the Restraint Chain and Restraint Hook are secured while the injector is under pressure. Do not rely on the Compression Gland to restrain the Solution Tube from retracting while in operation.
  • Do not over tighten the Compression Gland. Tighten only to the point where any leak stops. Over tightening the gland can, over time, cause damage to PVC/CPVC Solution Tubes as well as the Compression O-ring.
  • The pressure rating listed for this unit is the maximum operating pressure. It is highly recommended that the pressure in the main be reduced to an appropriately safe level before inserting or retracting the Solution Tube.
 

INSTALLATION INSTRUCTIONS  

WARNING: SAF-T-FLO injectors are shipped in their operating position. Removal of the solution tube may be required prior to installing the injector onto the main.

Step 1: Remove the Solution Tube

  • Loosen the Packing Nut by turning counter-clockwise.
  • Undo the (2) nuts securing the Upper Chain Plate to the Restraint Bolts.
  • Retract the Solution Tube from the Main Connection Assembly until the Limit Chain is completely extended. Loosen the Packing Nut more if needed.
  • Close the valve of the Flanged Ball Valve. If the valve does not want to close, ensure the Solution Tube has been retracted far enough so that the tip of the tube is not obstructing the valve from closing.
  • With the valve closed, disconnect the (2) Limit Chains from the Threaded Connectors attached to the Upper Chain Plate and completely remove the Solution Tube.

Step 2: Install the Flanged Ball Valve

WARNING: Do not use a pipe wrench to install the ball valve.
  • Install gasket appropriately and bolt to the flanged connection.
  • Make sure the Flanged Ball Valve is in the closed position.

Step 3: Install the Solution Tube

WARNING: For injectors not provided with a check valve, make sure to provide a suitable form of isolation to prevent back flow from the solution tube prior to opening the ball valve.
  • Insert the outlet end of the Solution Tube into the Packing Nut until the tip is stopped by the closed valve face.
  • Connect the (2) Limit Chains to the Threaded Connectors and close the jaw of the Threaded Connector.
  • SLOWLY OPEN the Ball Valve and begin to slide the Solution Tube down into the main. If water begins to leak past the Packing Nut, tighten until the leak stops.
  • Keep inserting the Solution Tube until the Upper Chain Plate is seated on the Restraint Bolts. Secure the Solution Tube into the operating position by securing the Upper Chain Plate to the Restraint Bolts with the nuts provided.
 
Retractable Injection Quill - 250psi, Flanged

COMPONENTS

Solution Tube Assembly

  1. Inlet Connection
  2. Upper Chain Plate
  3. Threaded Connectors (4x)
  4. Limit Chains (2x)
  5. Restraint Bolt Nut & Washer (2x)
  6. Solution Tube

Main Connection Assembly – Compression Gland

  1. Packing Nut, Lower Chain Plate, and Restraint Bolts
  2. Solution Tube Adapter
    *Compression O-ring not visible, located between Packing Nut and Solution Tube Adapter
  3. Guide Pipe

Main Connection Valve

  1. Flanged Ball Valve
  2. Main Connection Flange
 

For installation questions and assistance contact customer service at 1-800-957-2383

 